The factory made Reciprocating Packaged Chillers use best in class components.

Manufactured incorporating latest technology from world renowned Standard Refrigeration, USA!

State of art technology using most advanced heat exchanger tubes and baffle design makes the unit highly compact and heat transfer efficient.

Features :

Control Function : Remote 'on /off' of chillers and other equipment, sequencing of chillers and other equipment, ensure equal run hours, optimum starting and stopping of chillers as per load variation
Plant Viewer : Live Mimic of full plant i.e. all chillers, fans, AHUs, pumps, cooling towers, motorized valves etc, giving online Real Time data.
Chiller Viewer : Live mimic of individual chiller with (air) with chilled water inlet/outlet temperature; condenser air inlet /outlet temperature; suction, discharge, oil, net oil pressure; saturated suction & saturated discharge temperature; compressor current; No. of load/unload stages; compressor operating hours and No. of starts; on/off status of safety, motors, compressor, motorized valves of chillers.
Set Point Changing : Value of various set points can be changed through keyboard
Log Viewer : Data logging of above analog inputs, as storage in hard disk of PC or print form
Alarm Viewer : Gives the list of alarms with cause of tripping, date, time
Trend Viewer : Historical and real time processing of data for convenient analysis using time-based selection. This identifies discrepancies, energy consumption, load pattern on chiller based on compressor current, etc
Protection by Password : 3 level passwords used for prevention of unauthorized or unwanted access (i.e. Process Level, Engg. Level, Management Level)
Remote Access : Remote monitoring facility with PSTN (Public switching telephone network)(Optional)
Open System : Standard system is with MODBUS ASCII Protocol. Capable of working with variety of protocols, supports Ethernet /TCPIP, BACnet(Optional).
Time Scheduling : This allows central programming of all time-controlled functions. Operating schedule for one year using 7 days time program with additional overriding facilities for 15 holidays. This facility reduces day-to-day routine tasks of starting and stopping of plants.
Graphic Interface : Friendly and easy to operate
Graphic Engineering : The graphics package defines ability to define lines, boxes, circles, and arcs, free hand displays. It also allows to define points on the graphics where real time field data is displayed. Colours of symbols can be changed.

Technical Details

ACDR Series*   030 035 055 070 105
Nominal Capacity** TR 30 35 55 75 105
KW 105.5 123.0 193.4
246.2
369.3
KCAL/HR 90720 105840 166320 211680 317520
Compressor model   05040 05046 05066 05086 05126
Number of compressors   1 1 1 1 1
Compressor motor   IP 55 TEFC Squirrel cage induction motor suitable for 415 +/- 10% Volts, 3 phase 50 HzAC power supply
Type of starter   Star/Delta Star/Delta Star/Delta Star/Delta Star/Delta
Capacity control steps % of full capacity   100/75/50/25 100/75/50/25 100/83.3/ 66.7/33.3 100/75/50/25 100/83.3/ 66.7/33.3
Chiller model   10036LR1 10036LR1 10066 10070LR1 10126-2
No. of chillers   1 1 1 1 1
Chillers inlet/outlet nozzle NB inches 3 3 4 5 6
NB mm 80 80 100 125 150
Nominal chilled water flow rate GPM 72 84 132 168 252
Lts. per sec
4.55 5.30 8.33 10.61 15.91
Condenser module   9AV 30 9AV 35 9AV 30 9AV 30 9AV 30
Number of condenser modules   1 1 1 1 1
Condenser fan Diameter inches 31-1/2 31-1/2 31-1/2 31-1/2 31-1/2
mm 800
800
800
800
800
Number of condenser fans   2 2 4 4 6
Refrigerant R 22 charge (approx.) Lb. 66 77 132 154 220
Kg. 30 35 60 70 100
Unit Dimensions (in mm) Length 2535 2535 2950 2950 3710
Width 30 35 60 70 100
Height 30 35 60 70 100
Op.Weight (App.) Lb. 4851 5188 7144 8514 11363
Kg. 2205
2358 3247 3870 5165